MIL-DTL- 24784/11C(NAVY)
e.
Central control console (where applicable) - A description shall be given and illustrations included, where
specified:
(1) Location.
(2) Use of the unit (equipment or systems controlled or monitored).
(3) Any special features, such as:
(a)
Relinquishing control to a local switchboard.
(b) Automatic paralleling.
f.
Protective devices - A description shall be given and the following illustrations included:
(1) A circuit breaker coordination chart shall be prepared showing the time-current characteristics of all
the circuit breakers used in series from the generator to the load on a representative feeder. The bus
tie circuit breakers shall be plotted on log paper and shall cover the complete range from the long time
delay pickup value of current of the smallest breaker to the instantaneous trip point of the breaker with
the highest setting.
(2) The short circuit current characteristics of the generator shall also be shown on this chart. Following
are typical examples of the types, sizes, element ratings, and settings of the breaker circuits to be
covered for selective tripping:
(a)
Generator connection to switchboard.
(b) Bus tie.
(c)
Feeder.
(d) Main and branch.
(e)
Uses of fuses (on both power and lighting).
(f)
Design characteristics of controllers such as:
Manual operation.
1
Magnetic operation.
2
Low voltage protection.
3
Low voltage release.
4
g.
Lighting systems - A description shall be given and illustrations included as applicable:
(1) For ships with three decks or platform levels or less (excluding superstructure), a wiring deck plan of
the lighting systems shall be included.
(2) For all other ships, an isometric diagram of the lighting distribution system shall be included.
(3) Door switches and light traps for darkened ship operation.
(4) Red illumination, description of its operation, and use.
(5) Relay and portable lanterns, description of its operation, and use.
(6) Broad band blue illuminations, description of its operation, and use.
(7) Navigation and signal light:
(a)
Elementary wiring diagram.
(b) Outboard profile of the ship showing locations of the lights.
(c)
Operational procedures.
(8) Lights for night flight operations:
(a)
Elementary wiring diagram.
(b) Equipment and light location (including flight deck).
(c)
Operational procedures.
10